Wet Alarm Valve Flanged Ends SDH-AVA Model
Alarm Valve is a double seated clapper check valve with grooved seat design, which ensures positive water flow for alarm operation and is designed for installation in wet pipe sprinkler system. External bypass prevents false alarm under all supply pressure condition. In the event of variable pressure condition, false alarm is prevented with the provision of retard chamber, thus the design allows for installation under both variable and constant supply pressure condition. Operation of one or more automatic fire sprinklers causes the water to flow into the sprinkler system causing the alarm valve to open, allowing continuous flow of water into the system and transmittal of alarm, both electrical and mechanical.
- *
NOMINAL SIZE 200, 150, 100, & 80 NB
END CONNECTION Flange X Flange Flange X Groove Groove X Groove
MAXIMUM WORKING PRESSURE 17.5 Bar (250 PSI)*
THREADED OPENING BSPT
MOUNTING Vertical
FLANGE CONNECTION ANSI B16.42 #150 (Flange drilling mtaching to ANSI B 16.5 #150)
FACTORY HYDROSTATIC 35 Kg./ Sq.cm. (500PSI)